A relief fan that never stopped.

Elevator doors in a four-story office building were dragging, faulting and trapping occupants. The building was being pulled negative to outdoors — by a pressure relief fan running nonstop at full speed, and a toilet exhaust fan no control system knew was on.

Building
4-story concrete office, ~64,000 sf, Portland area
System
Central VAV air handler, plenum return, roof relief fan
Symptom
Elevator door faults and entrapments
Bluefin's role
Owner's representative & engineering advisory

The symptom

The elevators started faulting and trapping people. The elevator contractor inspected both cars and every landing door and concluded that excessive pressure across the hoistway was holding the doors from closing. The elevators were taken out of service until they could be confirmed safe.

The first suspect was the air handler's supply fan drive, which had tripped after a power event — leaving the exhaust fans running with no supply air. But entrapments had happened at other times too, so the drive trip couldn't be the whole story. The owner brought Bluefin in to find out what was.

What the BAS showed

On the building automation system's air handler graphic, nothing looked alarming: supply and relief fans running, the outside air damper at its 5% minimum, building pressure close to setpoint. What the screen didn't show:

As found vs. after commissioning

Air handler with an independent roof relief fan, shown as found and after commissioning OUTDOORS MECHANICAL ROOM — open return-air plenum OCCUPIED FLOORS 1–4 Return air dampers OA damper Filter HW CHW Supply fan AIR HANDLER Medium-pressure duct to VAV boxes Ceiling plenum → return shaft PRESSURE RELIEF FAN open to mech room TOILET CORE EXHAUST FAN From restrooms · constant ~8,000 cfm Not on the BAS — not on the graphic. Ran 24/7; no controls knew it was on. Now counted in the air balance — outside air sized to replace it. Running nonstop at 100% Min speed clamped at full speed; no pressure control, not just in economizer. Pulled plenum air straight outdoors. OA damper BAS graphic: 5% open. In the field: 100% closed — leakage only. Building pulled NEGATIVE to outdoors Toilet exhaust + relief fan far exceed outside air brought in. Pressure sensor sat in the return plenum, so the BAS didn't show it. Elevator doors Drag, fault, entrapments Back to a relief fan Locked out. Re-sequenced to run only in economizer mode, modulating on building pressure. Outside air = exhaust OA minimum set to match toilet exhaust, ~8,000 cfm. Building reads NEUTRAL Air in matches air out. Sensor relocated to occupied space; loop targets +0.01 in. w.c. to outdoors. Elevator doors No longer fighting building pressure

Simplified diagram, redrawn from the field BAS graphic. Building and owner not identified.

What was really happening

How the system is meant to work

The supply fan is the only fan in the air handler. It pushes air through medium-pressure duct to VAV boxes on each floor. Air returns through the ceiling plenum and up the shaft into the mechanical room, which is part of the return plenum. The supply fan draws it back through the return air dampers, mixes it with outside air, and supplies it again.

What the relief fan is for

The relief fan is independent of the air handler. In economizer mode, when extra outside air comes in, it relieves the surplus out of the plenum, modulating to hold building pressure. Run nonstop at full speed, it pulls the building negative.

Instead, two fans were exhausting at once — the relief fan pulling plenum air straight outdoors, and the toilet exhaust running unmonitored — while the outside air damper sat closed. With far more air leaving than coming in, the building made up the difference through every crack in the envelope and through the elevator hoistway. That pressure difference is what was holding the elevator doors.

The fix

  1. Relief fan locked out. It was running at 100% with no control, so the first step was to stop it.
  2. Outside air matched to exhaust. The air handler's minimum outside air was set to match the measured toilet exhaust, roughly 8,000 cfm, so air in equals air out.
  3. Pressure sensor moved to the occupied space. The building pressure reference now reads the space people actually occupy, with the loop targeting +0.01 in. w.c. to outdoors.
  4. Economizer sequence rewritten. A revised sequence was issued so the relief fan runs only in economizer mode, modulating on building pressure — and the air handler, relief fan and exhaust work together instead of against each other.
  5. Pressure monitoring installed. A differential pressure sensor in the hoistway core and building-pressure alarms in the sequence now alert the owner if the building drifts out of balance again.

The result

The building now reads neutral to outdoors. Outside air brought in matches what the exhaust removes, and the relief fan is back to its intended job. The underlying lesson: the controls were only managing the fans they knew about — and one of those was doing the wrong job.